Explosion protection |
|
|
Gas explosion protection |
II 2 G Ex de IIC T6 / T5 |
|
Dust explosion protection |
II 2 D IP 66 T80 °C / T95 °C |
Certificates |
PTB 05 ATEX 1071 |
Other certificates |
IECEx |
Rated values |
|
|
AC voltage |
250 V |
|
AC current |
9.0 A |
|
Frequency |
50 / 60 Hz |
|
DC voltage |
60 V |
|
DC current |
2.5 A |
|
|
Rated values depend on ambient temperatures and the connection cross-section
|
on connection cross-section |
a: 0.5 mm2 |
b: 0.75 mm2 |
c: 1.0 mm2 |
d: 1.5 mm2 | |
Enclosure material |
Connection chamber: polyamide (miniCLIX 8591: polyamide; brass, nickel-plated; stainless steel AISI 316L) |
Connectors |
Spring clamp connection 0.34 mm2 ... 1.5 mm2 (flexible or solid) |
Cable entries |
8592/...-..-...1
8592/...-..-...2 |
4 mm ... 7.5 mm
7.5 mm ... 11 mm | |
Ingress Protection |
IP 66 / IP 68 (2 m water column, 1 hour)
acc. to EN 60529
(with protective caps closed and secured as well as properly fitted and secured components) |
Safety class |
II - fulfilled by plastic versions
acc. to EN 60598 |
Ambient temperature |
see figure "Rated values" |
Storage temperature |
- 55 °C ... + 80 °C (in original packaging) |
Test torque |
Stopping plug screws pressure fitting with strain relief
protective cap
union nut |
1.5 Nm
2.5 Nm
2.5 Nm
2.5 Nm | |
Weight |
|
|
|
Plastic |
Metal |
Plug
Socket |
8592/.1.-..-....
8592/.2.-..-.... |
approx 0.168 kg
approx 0.164 kg |
approx 0.268 kg
approx 0.255 kg | |