Explosion protection |
|
|
Gas explosion protection |
II 2 G EEx de IIC |
|
Dust explosion protection |
I M 2 EEx de I |
Certificates |
|
|
Gas explosion protection |
DMT 02 ATEX E 026 |
|
Dust explosion protection |
LCIE 02 ATEX 6241 (see type 8146/5) |
Enclosure material |
Epoxy resin or polyester resin |
Main contacts |
3-pole |
Rated working voltage |
max. 690 V AC; 50 Hz / 60 Hz |
Rated working current |
0.1 A ... 25 A dependent on adjustment range |
Switching capacity |
abhängig vom gewählten Einstellbereich (AC)
230 V |
400 V |
500 V |
690 V |
6,4 kW |
11,4 kW |
14,4 kW |
20,0 kW | |
Thermal overcurrent trip |
Adjustable at switch; dependent on adjustment range |
Electromagnetic fast trip |
Adjustment range |
Threshold values set at factory |
0.16 A |
... |
0.63 A |
7.5 |
... |
12.0 In |
1.0 A |
... |
2.5 A |
9.0 |
... |
14.0 In |
4.0 A |
... |
6.0 A |
10.0 |
... |
15.0 In |
9.0 A |
... |
25.0 A |
12.0 |
... |
17.5 In | |
Back-up fuse |
Adjustment range
from ... to |
Highest rated current of the short circuit fuse if ICC > ICS |
at 230 V AC |
at 400 V AC |
at 440 V AC |
at 500 V AC |
at 690 V AC |
ICS |
gL, aM |
ICS |
gL, aM |
ICS |
gL, aM |
ICS |
gL, aM |
ICS |
gL, aM |
0.1 A ... 0.16 A
to
1.0 A ... 1.6 A |
short-circuit proof,
no fuse needed to ICC = 100 kA |
|
|
1.6 A ... 2.5 A |
|
|
|
|
40 kA |
25 A |
2.5 A ... 4.0 A |
60 kA |
35 A / 40 A |
10 kA |
40 A |
4.0 A ... 6.3 A |
70 kA |
50 A |
40 kA |
50 A |
7 kA |
40 A |
6.3 A ... 9.0 A |
50 kA |
80 A |
30 kA |
80 A |
5 kA |
50 A |
9.0 A ... 12.5 A |
75 kA |
80 A |
45 kA |
80 A |
27 kA |
80 A |
4.5 kA |
50 A |
12.5 A ... 16.0 A |
60 kA |
100 A |
40 kA |
100 A |
25 kA |
100 A |
4 kA |
50 A |
16.0 A ... 20.0 A |
55 kA |
100 A |
35 kA |
100 A |
22 kA |
100 A |
3.5 kA |
50 A |
20.0 A ... 25.0 A |
50 kA |
125 A |
30 kA |
125 A |
20 kA |
125 A |
3 kA |
50 A |
ICS = Breaking capacity of rated operating short circuit
ICC = Projected short circuit current at the installation location | |
Mechanical life |
105 operations |
Ambient temperature |
- 20 °C ... + 40 °C |
Terminal |
Main contacts |
1.5 mm2 ... 6 mm2 flexible
1.5 mm2 ... 10 mm2 solid |
Auxiliary contacts |
0.75 mm2 ... 1.5 mm2 flexible
0.75 mm2 ... 2.5 mm2 solid | |
Power dissipation |
max. 6.75 W |
Other features |
Switches are suitable for protection of "increased" safety motors; Switch operated by rotary actuator; clearly visible position indication; Phase failure sensivity. Due to shortened switch grip, release is ensured even if mechanism is locked. Breaking parameter: can be used as MAIN or EMERGENCY OFF switch. If necessary accessories are fitted. |
Handle |
Labelling: |
0-I; 0-position can be padlocked in 3 positions |
Colour: |
Standard: grip and collar black |
Special: red grip and yellow collar (EM-STOP function) | |
Accessories |
|
|
Auxiliary contacts |
Options: none; 1 NC + 1 NO; 2 NC + 2 NO |
|
Rated current |
AC 15 |
230 V |
|
400 V |
|
2 A |
|
1 A |
DC 13 |
60 V |
110 V |
220 V |
|
2.5 A |
0.6 A |
0.25 A | |
|
Rated voltage |
max. 500 V AC |
|
Undervoltage trip |
|
|
|
Function |
When power is lost, circuit-breaker trips; this prevents unwanted restarting, e.g. of a motor |
|
|
Voltages |
available control voltage UC 50 Hz: 48 V; 60 V; 110 V; 230 V; 400 V; 415 V; 500 V
Pick-up 0.85 ... x UC
Drop-out 0.7 ... 0.35 x UC |
|
Shunt trip |
|
|
|
Function |
For remote tripping of circuit-breaker; remote tripping by applying actuating voltage |
|
|
Voltages |
available control voltage UC AC / DC: 24 V ... 60 V; 110 V ... 240 V |