The enclosures are used to build motor starters, control stations and terminal boxes. Furthermore they are suitable for measuring equipment and customer specific control units. By using this technology the installation of sparcing and arcing equipment in a Zone 1 or Zone 2 application is enabled. Therefore just standard industrial electrical components are used. This equipment is engineered and wired according to customer’s requirement. Optionally the enclosure can be mounted in an "Increased Safety" control panel as module for lighting and heating distribution panels.
The design of the enclosure is optimised for:
- simple installation and commissioning
This is achived by the big cover opening. Therefore the complete mounting slot for the electrical components is freely accessable. Covers with windows and O-Ring seals together with mounting plates and DIN rails are available to complete the series of enclosures.
For direct cable entry flameproof cable glands or threaded entries for direct conduit connection can be applied. For indirect cable entry connection chambers - type 8146 and 8125 - come into use.
Zones 1 & 2
Version |
Series 8265 |
Gas explosion protection |
II 2G Ex d IIC T4 ... T6 |
Certificates |
8265/2: PTB 06 ATEX 1023 U
8265/3: PTB 06 ATEX 1023 U
8265/4: PTB 06 ATEX 1076 U
8265/6: |
Other certificates |
IECEx, UL |
Rated operational voltage Ue |
Standard: |
max. 1100 V |
Option: |
up to 10 kV | |
Rated working current Ie |
Enclosure |
Current |
Size 2 Size 3 Size 4 |
max. 160 A |
Size 6 |
max. 250 A | |
Degree of protection |
IP 54
IP 66 (with additional O-gasket) |
Housing |
aluminium, copper free (saltwater-proof) |
Power loss and temperature class |
Enclosure |
for ambient temperature 40 oC |
T6 |
T5 |
Size 2 |
30 W |
45 W |
Size 3 |
43 W |
63 W |
Size 4 |
62 W |
93 W |
|
for ambient temperature 55oC |
T6 |
T5 |
Size 2 |
18 W |
30 W |
Size 3 |
26 W |
43 W |
Size 4 |
35 W |
62 W | |
Maximal number of drillings |
Maximal number of metrical drillings at each side |
Enclosure |
M 20 |
M 25 |
M 32 |
M 40 |
M 50 |
M 63 |
M 75 |
Size 2 |
3 |
2 |
2 |
1 |
|
|
|
Size 3 |
8 |
4 |
3 |
2 |
1 |
1 |
1 |
Size 4 |
16 |
9 |
6 |
4 |
3 |
1 |
1 | |
Maximal number of conduit drillings |
Maximal numbers of Conduit-drillings at each side |
Enclosure |
1/4" |
3/8" |
1/2" |
3/4" |
1" |
1 1/4" |
1 1/2" |
2" |
Size 2 |
8 |
8 |
4 |
3 |
2 |
2 |
1 |
- |
Size 3 |
16 |
16 |
9 |
6 |
5 |
3 |
2 |
1 |
Size 4 |
36 |
36 |
18 |
16 |
9 |
6 |
5 |
3 | |
KAT-TD
Technical Data |
Version |
EEx e enclosure 8146 |
Explosion protection |
|
|
Gas explosion protection |
II 2 G EEx edmq ia / ib [ia / ib] IIA, IIB resp. IIC T6, T5 resp. T4 |
Certificates |
|
|
Gas explosion protection |
PTB 01 ATEX 1024
IECEx PTB 06.0090 |
Material |
|
|
Housing |
Polyester resin, glass fibre-reinforced, dark grey, similar to RAL 7024, impact strenght ≥ 7 Nm, surface resistance ≤ 109 Ohm, material flame resistant, self-extinguishing |
|
Gaskets |
Polyurethane, foam |
Degree of protection |
IP 66 (dependent on equipment installed) |
Rated working voltage |
max. 1100 V (dependent on equipment installed) |
Rated working current Ie |
max. 630 A |
KAT-TD
Technical Data |
Version |
EEx e enclosure 8125 |
Explosion protection |
|
|
Gas explosion protection |
II 2 G EEx edmq [ia/ib] IIA resp. IIB T6, T5 resp. T4 |
Certificates |
|
|
Gas explosion protection |
PTB 01 ATEX 1001
IECEx PTB 06.0079 |
Material |
|
|
Housing |
dependent on version selected:
sheet steel, glavanized; painted light grey, RAL 7032 or
stainless steel without paint (paint finish can be ordered) |
|
Gaskets |
Polyurethane, foam |
Degree of protection |
IP 66 (dependent on equipment installed) |
Rated working voltage |
max. 1100 V (dependent on equipment installed) |
Rated working current Ie |
max. 630 A |
Dimension drawings (all dimensions in mm) - subject to alterations |
|
|
|
|
|
|
|
|
|
|
Enclosure size 2 8265/02-... |
|
|
Enclosure size 3 8265/03-... |
|
|
|
|
|
|
|
|
|
|
|
Enclosure size 4 8265/04-... |
|
|
Enclosure size 6 8265/06-... |
|
|
|
|
|
|
|
|
Enclosure Series 8265 |
|
|
|
|
|