Grounding monitoring devices ensure that road tanker and tank wagons are electrostatically grounded correctly during the loading or unloading of flammable liquids. The device provides a conductive connection to the ground and monitors in parallel the quality of the electrostatic grounding. The electrostatic charge of the tank is kept on a safe level.
An occasional discharge in conjunction with a spark is prevented and therefore the explosion protection ensured.
The grounding monitoring device UZCL 3.d is able to distiguish
between the correct grounding of road tankers and the incorrect grounding of other items, e.g. tank platform. If the pliers are
connected to a road tanker the green light switched on and the
relay will be energized. The contacts of the relay can be used to control e.g. a valve or to trigger an alarm.
The following recommendations demand the grounding of tank
vehicles during the loading or unloading procedure and endorse that interlocks should be provided to prevent loading when the grounding cable is not connected.
- CENELEC CLC/TR 50404 Code of practice for the avoidance
of hazards due to static electricity
- National Fire Protection Association NFPA77
Recommended practice of static electricity 2000 edition
Zones 1 & 2
Certificates |
FTZU 03 ATEX 0213 X (UZCL 3.d; IP 54)
FTZU 06 ATEX 0015 (UZCL 4.d; IP 65) |
Other certificates |
GOST R (Russia) |
Explosion protection |
II 2 G EEx d [ib] IIB T4 |
Installation |
in Zone 1, Zone 2 |
Ambient temperature |
- 50 °C ... + 60 °C (IP 65: - 20 °C ... 40 °C) |
Storage temperature |
- 50 °C ... + 60 °C |
Ingress Protection |
IP 54 (UZCL 3.d)
IP 65 (UZCL 4.d) |
Rated voltage |
230 V |
Frequency |
50 Hz |
Power consumption |
10 VA |
LED indication |
Operating principle: |
State of grounding process |
|
Reaction of grounding device |
|
Clamp is not connected, grounding equipment not in use |
Grounding incorrect
- red light ON
- green light OFF
- contacts OPEN
|
|
Clamp connected directly to the ground, e.g. via loading platform |
Grounding incorrect
- red light ON
- green light OFF
- contacts OPEN
|
|
Clamp connected to the road tanker |
Grounding correct
- red light OFF
- green light ON
- contacts CLOSED
|
|
Clamp connected to the road tanker. The road tanker is grounded consecutively (e.g. with the loading arm) |
Grounding correct
- red light OFF
- green light ON
- contacts CLOSED
| |
Control contacts |
|
|
Switching capacity |
230 V / 3 A |
Material |
|
|
Housing |
steel ST37 acc. to DIN |
|
Clamp |
pressed galvanised steel, contact point in copper |
Cable length |
10 m (other length or cable on request), see selection table |
Cable glands |
HØ7RN-F 3G x 1,5 mm cable diameter 8,5 mm - 16 mm |
Dimension drawings (all dimensions in mm) - subject to alterations |
|
|
Grounding monitoring device Series UZCL |
Cable reel with self retracting reel |