Explosion protection |
|
|
Gas explosion protection |
II 2 G EEx de IIC T.
Type |
Adjustment range |
Temperature class |
Tmax. |
8527/21
8527/22 |
0.1 A up to 0.25 A
0.25 A up to 12.5 A
12.5 A up to 16 A |
T6
T5
T4 |
80 °C
95 °C
130 °C |
8527/23 |
0.1 A up to 12.5 A |
T6 |
80 °C |
8527/24 |
16 A up to 22.5 A |
T5 |
95 °C | |
|
Dust explosion protection |
II 2 D IP 65 T80 °C, T95 °C, T130 °C |
Certificates |
|
|
Gas explosion protection |
DMT 02 ATEX E 026 |
|
Dust explosion protection |
LCIE 02 ATEX 6241 (see type 8146/5) |
Enclosure material |
Polyester resin, dark grey similar to RAL 7024, Surface resistance ≤ 109 ohms; impact strength ≥ 7 Nm, Material self-extingguishing and flame resistant to IEC-92-1, UL 94, ASTM D 635-77 |
Mounting position |
any |
Degree of protection |
IP 66 |
Switch element |
|
|
Main contacts |
3 pole |
|
Rated working voltage |
max. 690 V, AC, 50 Hz / 60 Hz |
|
Rated operating current |
0.1 A ... 22.5 A |
|
Switching capacity |
according to adjustment range (AC)
230 V |
400 V |
500 V |
690 V |
6.4 kW |
11.4 kW |
14.4 kW |
20.0 kW | |
|
Thermal overcurrent trip |
according to adjustment range, adjustment at switch |
|
Electromagnetic fast trip |
Adjustment range |
Threshold values set at factory |
0.16 A |
... |
0.63 A |
7.5 |
... |
12.0 In |
1.0 A |
... |
2.5 A |
9.0 |
... |
14.0 In |
4.0 A |
... |
6.0 A |
10.0 |
... |
15.0 In |
9.0 A |
... |
25.0 A |
12.0 |
... |
17.5 In | |
|
Back-up fuse |
Adjustment range
from ... to |
Highest rated current of the short circuit fuse if ICC > ICS |
at 230 V AC |
at 400 V AC |
at 440 V AC |
at 500 V AC |
at 690 V AC |
ICS |
gL, aM |
ICS |
gL, aM |
ICS |
gL, aM |
ICS |
gL, aM |
ICS |
gL, aM |
0.1 A ... 0.16 A
to
1.0 A ... 1.6 A |
short-circuit proof,
no fuse needed to ICC = 100 kA |
|
|
1.6 A ... 2.5 A |
|
|
|
|
40 kA |
25 A |
2.5 A ... 4.0 A |
60 kA |
35 A / 40 A |
10 kA |
40 A |
4.0 A ... 6.3 A |
70 kA |
50 A |
40 kA |
50 A |
7 kA |
40 A |
6.3 A ... 9.0 A |
50 kA |
80 A |
30 kA |
80 A |
5 kA |
50 A |
9.0 A ... 12.5 A |
75 kA |
80 A |
45 kA |
80 A |
27 kA |
80 A |
4.5 kA |
50 A |
12.5 A ... 16.0 A |
60 kA |
100 A |
40 kA |
100 A |
25 kA |
100 A |
4 kA |
50 A |
16.0 A ... 20.0 A |
55 kA |
100 A |
35 kA |
100 A |
22 kA |
100 A |
3.5 kA |
50 A |
20.0 A ... 25.0 A |
50 kA |
125 A |
30 kA |
125 A |
20 kA |
125 A |
3 kA |
50 A |
ICS = Breaking capacity of rated operating short circuit
ICC = Projected short circuit current at the installation location | |
|
mechanical |
105 operations |
|
Ambient temperature |
- 20 °C ... + 40 °C ...
- 40 °C ≤ Ta ≤ 55 °C |
|
Handle |
Labeling: 0 - I; in 0-position can be padlocked in 3 positions
Colour:
Standard: Grip black, collar black
Special: Red grip and yellow collar (EM-STOP) |
Accessories |
|
|
Auxiliary contacts |
Option: None; 1 NC + 1 NO; 2 NC + 2 NO |
|
Rated working current |
AC 15: |
24 V / 2.5 A |
230 V / 2 A |
400 V / 1 A |
|
|
DC 13: |
24 V / 2.5 A |
60 V / 2.5 A |
110 V / 0.6 A |
220 V / 0.25 A |
440 V / - A | |
|
Undervoltage trip |
|
|
|
Function |
When power is lost, circuit-breaker trips; this prevents unwanted restarting, e.g. of a motor |
|
|
Pick-up voltage |
≥ 0.85 x Uc |
|
|
Drop-out |
0.7 ... 0.35 x Uc |
|
|
Power consumption |
|
|
|
|
Inrush |
0.9 VA |
|
|
|
Holding |
0.9 VA |
|
Shunt trip |
|
|
|
Function |
For remote tripping of circuit-breakers by applying actuating voltage |
|
|
Pick-up voltage |
≥ 0.85 x Uc |
|
|
Relative duty cycle |
Switches itself off automatically via integrated contact switch |
|
|
Power consumption |
|
|
|
|
Inrush |
24 - 60 V: 14,4 - 90 VA; 110 - 240 V: 13 - 61 VA; 220 - 415 V: 17,6 - 62,3 VA |
|
|
|
Holding |
Switches itself off automatically via integrated contact switch |
|
Ammeter |
|
|
|
Version |
Type 8405; dimensions 64 mm x 64 mm |
|
|
Movement |
Moving iron: class 2.5; direct measuring; overload scale 1:2 |
|
|
Measuring range |
Dependent on switch setting range |
|
|
Overload capacity |
2 x Ie 25 s; 50 x Ie 1 s |
Connections |
8527/21
8527/22 |
directly to fitted components |
Main contacts |
1.5 mm2 ... 6 mm2 flexible
1.5 mm2 ... 10 mm2 solid |
Auxiliary contacts |
0.75 mm2 ... 1,5 mm2 flexible
0.75 mm2 ... 2,5 mm2 solid |
8527/23
8527/24
8527/25
8527/26 |
on terminals |
0.5 mm2 ... 6 mm2 flexible
0.5 mm2 ... 10 mm2 solid |
Please note:
Compare cable diameter with cable diameter range of cable entries | |